Features
1.Low self discharge characteristic
2.Non-Spillable construction design
3.Sealed and maintenance free operation
4.Safety valve installation for explosion proof
5.Exceptional deep discharge recovery performance
6.ABS containers and covers(UL94HB, UL94V-0) optional
Application:
1. Solar and wind energy storage system
2. EPS and UPS battery backup
3. Signal system , emergency lighting system , security system
4. Telecommunication Equipment
5. Power plant and transmission system
Nominal Voltage |
12 V |
|
Capacity (25℃) |
4AH---250AH |
|
Internal resistance (Fully charged, 25℃) |
Approx. 6.5mΩ |
|
Capacity affected by temperature (10HR) |
40℃ |
102% |
25℃ |
100% |
|
0℃ |
85% |
|
-15℃ |
65% |
|
Self-discharge (25℃) |
3 month |
Remaining Capacity: 91% |
6 month |
Remaining Capacity: 82% |
|
12 month |
Remaining Capacity: 65% |
|
Nominal operating temperature |
25℃±3℃(77℉±5℉) |
|
Operating temperature range |
Discharge |
-15℃~50℃(5℉~122℉) |
Charge |
-10℃~50℃(14℉~122℉) |
|
Storage |
-20℃~50℃(-4℉~122℉) |
|
Float charging voltage(25℃) |
13.50 to 13.80V Temperature compensation:-18mV/℃ |
|
Cyclic charging voltage(25℃) |
14.50 to 14.90V Temperature compensation:-30mV/℃ |
|
Maximum charging current |
16.5A |
|
Terminal material |
Copper |
|
Maximum discharge current |
550A(5 sec.) |
|
Designed floating life(20℃) |
12 years |
http://www.yingyedabattery.com/